Part No.: MPHS-COMX-51CA-RE
PROFINET IO-Device :The module for all communication tasks
The comX communication module has been designed to be integrated into automation devices e.g. robot controllers, PLCs or drives to add a network interface. All communication tasks are executed autonomously within the module - irrespective of the processor of the target device.
Process data is exchanged via a Dual-Port-Memory which is accessed either by an 8-/16-bit bus interface or a fast 50 MHz SPI interface.
comX supports all major Real-Time Ethernet protocols as Master or Slave and covers all network-specific demands in just one single module. To support a line topology, the module is equipped with two Ethernet ports. The communication protocol can be changed simply and reliably by loading the appropriate firmware and a software license for masters.
Product | Part Number | 1571.100 |
---|---|---|
Brief Description | Communication Module Real-Time Ethernet | |
Communication Controller |
netX: netX 51 | |
Integrated Memory |
RAM: 8 MB SDRAM FLASH: 4 MB serial Flash |
|
Power Supply |
Supply voltage: +3.3 V DC ± 5 % Typical/maximum current: approx. 530 mA/580 mA (at 3.3 V) Typical power consumption: approx. 1.9 W Power connector: via system bus connector X1 |
|
System Interface |
Type: Parallel or serial dual-port memory interface Connector: 50-pin SMT, female connector Pin distance: 1.27 mm Dual-port memory size: 16 KByte Data width: 8/16 bit Serial dual-port memory interface: SPI Slave, mode 3 Baud rate: max. 50 MHz |
|
Communication Interface |
Communication standard: Ethernet Interface type: 10BASE-T/100BASE-TX, potential-free Auto negotiation: supported Auto cross over: supported Connector: 2 * RJ45 socket |
|
Diagnostic Interface |
Type: UART or USB Connector: Signal at host interface. Available only if integrated in host system. |
|
Display |
LED display:
|
|
Environment |
Ambient temperature range for operation: 0 °C ... +65 °C (Air flow during measurment: 0,5 m/s) Ambient temperature range for storage: -10 °C … +70 °C Humidity range: 10 % … 95 % relative humidity (non-condensing) |
|
Device |
Dimensions (L x W x H): 70 mm x 30 mm x 21.5 mm Weight: approx. 35 g ... 40 g Mounting: using screwable metal bolts, according to comX Design Guide |
|
Configuration | Configuration software: SYCON.net | |
Conformity | RoHS: yes | |
Conformance with EMC Directives |
CE sign: yes Emission: EN 61000-6-4 Immunity: EN 61000-6-2 Electrostatic discharge (ESD) according to EN 61000-4-2 (Contact discharge method): EN 61000-4-2: ± 6 kV, Criterion B Fast transient interferences (Burst) according to EN 61000-4-4: EN 61000-4-4: ± 2.2 kV, Criterion B (Communication lines, shielded) Surge voltage according to EN 61000-4-5 (Communication and data lines): EN 61000-4-5: 1 kV, Criterion A (Communication lines, shielded) |